Analyze this law with AI1 (1) The following definitions apply in these Regulations.
Act means the Canada Shipping Act, 2001. (Loi)
cargo vessel means a vessel that is not a passenger vessel. (bâtiment de charge)
dangerous goods means the substances, materials and articles to which the IMDG Code applies. (marchandises dangereuses)
fire retardant coating means a coating that
(a) a product certification body, testing laboratory or recognized organization has certified as having a flame spread rating or index of 25 or less and a smoke developed classification or index of 100 or less when tested in accordance with the standard CAN/ULC-S102, entitled Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies, published by the Standards Council of Canada, or the standard ASTM E84, entitled Standard Test Method for Surface Burning Characteristics of Building Materials; or
(b) meets the flame spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code. (revêtement retardant la propagation de la flamme)
fire retardant resin means a laminating resin that
(a) a product certification body, testing laboratory or recognized organization has certified as having a flame spread rating or index of 25 or less and a smoke developed classification or index of 100 or less when tested in accordance with the standard CAN/ULC-S102, Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies, published by the Standards Council of Canada, or the standard ASTM E84, entitled Standard Test Method for Surface Burning Characteristics of Building Materials; or
(b) meets the flame spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code. (résine retardant la propagation de la flamme)
fishing vessel has the same meaning as in subsection 1(1) of the Marine Personnel Regulations. (bâtiment de pêche)
FSS Code means the International Code for Fire Safety Systems, published by the IMO. (Recueil FSS)
FTP Code means the International Code for Application of Fire Test Procedures, 2010, published by the IMO. (Code FTP)
high-speed craft means a craft that has been certified in accordance with the HSC Code and that meets the requirements of that Code. (engin à grande vitesse)
HSC Code means
(a) in the case of high-speed craft referred to in sections 1.3.1 to 1.3.6 of the International Code of Safety for High Speed Craft, 2000, published by the IMO, that Code; and
(b) in the case of all other high-speed craft, the International Code of Safety for High-Speed Craft, 1994, published by the IMO. (Recueil HSC)
IMDG Code means the International Maritime Dangerous Goods Code, published by the IMO. (Code IMDG)
IMO means the International Maritime Organization. (OMI)
length has the same meaning as in paragraph (b) of the definition length in section 1 of the Vessel Registration and Tonnage Regulations. (longueur)
Minister means the Minister of Transport. (ministre)
near coastal voyage, Class 2, limited means a voyage
(a) that is not a sheltered waters voyage;
(b) during which the vessel engaged on the voyage is always within 5 nautical miles from shore in waters contiguous to Canada, the United States (except Hawaii) or Saint Pierre and Miquelon;
(c) during which the maximum distance from the port of call is not more than 7.5 nautical miles, if the voyage starts and ends at the same port of call; and
(d) during which the maximum distance between all ports of call is not more than 15 nautical miles, if the voyage starts and ends at different ports of call. (voyage limité à proximité du littoral, classe 2)
passenger vessel means a vessel that carries more than 12 passengers. (bâtiment à passagers)
product certification body means a body that is accredited by the Standards Council of Canada, or by any other national accreditation organization that is a member of the International Accreditation Forum Multilateral Recognition Arrangement (MLA), to give third-party written assurance that a product meets the specified requirements for the product, including initial certification and maintenance of that certification. (organisme de certification de produits)
recognized organization means an organization or a corporation with which the Minister has entered into an agreement or arrangement under paragraph 10(1)(c) of the Act. (organisme reconnu)
sheltered waters voyage has the same meaning as in section 1 of the Vessel Safety Certificates Regulations. (voyage en eaux abritées)
SOLAS means the International Convention for the Safety of Life at Sea, 1974, and the Protocol of 1988 relating to the Convention. (SOLAS)
testing laboratory means a laboratory that is accredited by the Standards Council of Canada, or by any other national accreditation organization that is a member of the International Laboratory Accreditation Cooperation, to produce accurate results for the specific tests or calibrations that are listed on its Scope of Accreditation. (laboratoire d’essai)
type approval certificate means a type approval certificate referred to in the FTP Code. (certificat d’approbation par type)
(2) Except as provided in subsection (3), all words and expressions defined in Chapter II-2 of SOLAS and used in Part 1 or 2 have the same meaning as in that Chapter.
(3) For the purposes of Parts 1 and 2, the definition “A” class divisions includes the criterion that the insulation on the decks and bulkheads be held in place in accordance with the applicable requirements of the type approval certificate and with the manufacturer’s instructions.
(4) For the purposes of Parts 1 and 2, a vessel is constructed on
(a) the earliest of
(i) the day on which its keel is laid,
(ii) the day on which construction identifiable with a specific vessel begins, and
(iii) the day on which assembly of the vessel reaches the lesser of 50 tonnes and 1% of the estimated mass of all structural material; or
(b) in the case of a vessel converted to a passenger vessel, the day on which the conversion begins.
(5) Except as otherwise indicated in these Regulations, any reference in these Regulations to a document is a reference to the document as amended from time to time.
(6) For the purpose of interpreting a document incorporated by reference into these Regulations,
(a) “should” is to be read as “must”; and
(b) “Administration” is to be read as “Minister”.
(7) For the purposes of these Regulations, any guidelines, recommendations, requirements and similar matters set out in a document referred to in a footnote to a document that is incorporated by reference into these Regulations are to be considered mandatory.
(8) For the purposes of these Regulations, dangerous goods are in limited quantities if Chapter 3.4 of the IMDG Code applies to those goods and they meet the requirements of that Chapter.
2 (1) For the purposes of these Regulations, if a material must meet requirements set out in Annex 1 to the FTP Code,
(a) it must be approved by the Minister as meeting those requirements and in accordance with that Code;
(b) the Minister’s approval is not required when section 6 of the Code applies; and
(c) the Code is to be read without reference to the words “In general”.
(2) For the purposes of these Regulations,
(a) “may” is to be read as “must” in section 3.4 of Part 3 of Annex 1 to the FTP Code;
(b) section 3.5.2.1 of Part 3 of Annex 1 to the FTP Code is to be read as “Thermal radiation through windows must be tested and evaluated in accordance with appendix 3 to this part if escape routes pass near the windows”; and
(c) the hose-stream test procedure set out in section 5 of appendix 2 to Part 3 of Annex 1 to the FTP Code is mandatory if escape routes pass near the windows.
3 (1) For the purposes of these Regulations, if a system or equipment must meet requirements of the FSS Code, the system or equipment must be approved by the Minister as meeting those requirements.
(2) Subsection (1) does not apply in respect of the design of pressure containers referred to in section 124.
100 (1) The following definitions apply in this Part.
equipment includes appliances. (équipement)
inland voyage has the same meaning as in section 1 of the Vessel Safety Certificates Regulations. (voyage en eaux internes)
near coastal voyage, Class 1 has the same meaning as in section 1 of the Vessel Safety Certificates Regulations. (voyage à proximité du littoral, classe 1)
near coastal voyage, Class 2 has the same meaning as in section 1 of the Vessel Safety Certificates Regulations. (voyage à proximité du littoral, classe 2)
unlimited voyage has the same meaning as in section 1 of the Vessel Safety Certificates Regulations. (voyage illimité)
(2) For the purposes of this Part, a reference to “near coastal voyage, Class 2” must be read as including a reference to “inland voyage”.
101 (1) This Part applies in respect of Canadian vessels everywhere that are
(a) passenger vessels that are Safety Convention vessels;
(b) passenger vessels that are not Safety Convention vessels and are
(i) 24 m or more in length, other than vessels referred to in paragraph (2)(a), or
(ii) more than 15 gross tonnage but of less than 24 m in length that are carrying more than 36 berthed passengers;
(c) cargo vessels of 500 gross tonnage or more; or
(d) vessels of more than 15 gross tonnage that carry dangerous goods, other than in limited quantities, and that are referred to in regulation 19.2.2 of Chapter II-2 of SOLAS or have cargo spaces referred to in that regulation.
(2) This Part, other than the requirements with respect to structural fire protection, applies in respect of Canadian vessels everywhere that are
(a) passenger vessels of 24 m or more in length that
(i) are not Safety Convention vessels,
(ii) are carrying no berthed passengers and fewer than 100 unberthed passengers, and
(iii) are engaged on a sheltered waters voyage or a near coastal voyage, Class 2, limited; or
(b) cargo vessels of 24 m or more in length but of less than 500 gross tonnage, other than vessels that carry dangerous goods, other than in limited quantities, and that are referred to in regulation 19.2.2 of Chapter II-2 of SOLAS or have cargo spaces referred to in that regulation.
(3) This Part does not apply in respect of
(a) pleasure craft;
(b) fishing vessels;
(c) high-speed craft;
(d) vessels that do not have mechanical means of propulsion;
(e) wooden vessels of primitive build;
(f) vessels that are capable of engaging in the drilling for, or the production, conservation or processing of, oil or gas; or
(g) nuclear vessels.
102 (1) Except as otherwise provided in this Part, a vessel’s authorized representative must ensure that the requirements of Chapter II-2 of SOLAS — other than those of regulations 1.1 and 1.3 to 1.6 and of Part E — and the requirements of sections 109 to 150 and 153 to 159 are met in respect of the vessel.
(2) Except as otherwise provided in this Part, a vessel’s master must ensure that the requirements of regulation 7.8.1 and Part E of Chapter II-2 of SOLAS and of sections 117, 118, 151 and 152 are met in respect of the vessel.
(3) For the purposes of subsection (1), in respect of vessels that are not Safety Convention vessels,
(a) the construction requirements set out in Chapter II-2 of SOLAS for vessels carrying more than 36 passengers apply in respect of vessels referred to in paragraph 101(1)(b) that
(i) are carrying more than 36 berthed passengers,
(ii) are carrying more than 50 passengers, of which more than 12 but not more than 36 are berthed passengers, or
(iii) are carrying more than 100 passengers and are engaged on a voyage that is not a sheltered waters voyage or a near coastal voyage, Class 2, limited; and
(b) the construction requirements set out in Chapter II-2 of SOLAS for vessels carrying not more than 36 passengers apply in respect of vessels referred to in subparagraph 101(1)(b)(i) that
(i) are carrying not more than 50 passengers, of which not more than 36 are berthed passengers,
(ii) are carrying not more than 100 passengers, of which not more than 12 are berthed passengers, and are engaged on a voyage that is not a sheltered waters voyage or a near coastal voyage, Class 2, limited, or
(iii) are carrying more than 100 passengers, of which not more than 12 are berthed passengers, and are engaged on a voyage that is a sheltered waters voyage or a near coastal voyage, Class 2, limited.
(4) Despite subsections (1) and (2), the requirements for tankers that are set out in Chapter II-2 of SOLAS — other than those in regulation 1 — apply in respect of tankers subject to regulation 1.6 of that Chapter. The authorized representative of a tanker must ensure that any requirements of that regulation that are in addition to or different from the requirements referred to in those subsections are met. However, the requirement in regulation 1.6.7 of that Chapter that equipment be fitted not later than July 1, 2005 does not apply before
(a) if the tanker is a Safety Convention vessel, the day on which it is first registered as a Canadian vessel or the day on which this section comes into force, whichever is later;
(b) if the tanker is not a Safety Convention vessel, the day on which it is first registered as a Canadian vessel or the first anniversary of the day on which this section comes into force, whichever is later; and
(c) if the tanker is transferred from the register of another state to the Register for the first time on the day on which this section comes into force, the day on which it is transferred to the Register.
103 If a vessel that is not a Safety Convention vessel and that was constructed before the day on which this section comes into force held, at any time before that day, a certificate issued under the Vessel Certificates Regulations or under section 318 or 319 of the Canada Shipping Act, R.S.C., 1985, c. S-9, its authorized representative may ensure that the requirements with respect to structural fire protection and fire safety systems and equipment that would have been required under the Act to be met, on the day before that day, are met instead of the requirements referred to in section 102 of these Regulations with respect to structural fire protection and fire safety systems and equipment.
104 If a Safety Convention vessel that was constructed before July 1, 2002 held, at any time before the day on which this section comes into force, a certificate issued under the Vessel Certificates Regulations or under section 318 or 319 of the Canada Shipping Act, R.S.C., 1985, c. S-9,
(a) its authorized representative may ensure that the requirements with respect to structural fire protection and fire safety systems and equipment that would have been required under the Act to be met, on the day before that day, are met instead of the requirements referred to in section 102 of these Regulations with respect to structural fire protection and fire safety systems and equipment; and
(b) its master may ensure that the requirements with respect to fire control plans that would have been required under the Act to be met, on the day before that day, are met instead of the requirements referred to in section 102 of these Regulations with respect to fire control plans.
105 For the purposes of sections 103 and 104, the reference to section 318 or 319 of the Canada Shipping Act, R.S.C., 1985, c. S-9, includes any predecessor enactment relating to the same subject matter.
106 (1) Except in respect of the requirements referred to in subsection (3), sections 103 and 104 do not apply in respect of
(a) parts of a vessel that, beginning on the day on which this section comes into force, undergo repairs, alterations or modifications that
(i) substantially alter the vessel’s dimensions or its passenger accommodation spaces, or
(ii) substantially increase the vessel’s service life or the life of the vessel’s outfitting;
(b) systems and equipment that are related to the parts of a vessel described in paragraph (a);
(c) parts of a vessel that, beginning on the day on which this section comes into force, are replaced; or
(d) systems and equipment that, beginning on the day on which this section comes into force, are replaced.
(2) Sections 103 and 104 do not apply if the vessel’s intended service changes in such a manner that any of the requirements with respect to structural fire protection and fire safety systems and equipment that would have been required under the Act to be met are no longer met.
(3) Sections 103 and 104 apply only until the first anniversary of the day on which this section comes into force in respect of the requirements of regulations 13.3.4.2 to 13.3.4.5 and 13.4.3 and part E — except regulations 16.3.2.2 and 16.3.2.3 — of Chapter II-2 of SOLAS.
(4) Sections 103 and 104 do not apply in respect of amendments to SOLAS that are adopted by the IMO on or after the day on which this section comes into force if SOLAS provides that the amendments apply regardless of the date of a vessel’s construction.
107 For the purposes of this Part, the Marine Technical Review Board established under section 26 of the Act may exercise the Administration’s powers conferred by regulations 4 and 5 of Chapter I of SOLAS.
108 (1) A vessel that carries dangerous goods must hold a Document of Compliance issued under subsection (2).
(2) On application by the authorized representative of a vessel, the Minister must issue a Document of Compliance to the vessel if its construction and equipment meet the requirements referred to in section 102 that apply if the vessel carries dangerous goods.
(3) For the purposes of this section, dangerous goods does not include
(a) dangerous goods in limited quantities; or
(b) dangerous goods specified as class 6.2 or 7 in the IMDG Code, except solid bulk cargoes.
109 For the purposes of regulation 4.2.2.3.5.1, if sounding pipes are used, they must terminate on an open deck, if feasible.
110 For the purposes of regulation 4.2.2.4, the air pipes on any oil tank or part of the oil fuel system must be flame-screened and, if feasible, terminate on an open deck.
111 The mechanical ventilation system required by regulation 4.5.4.1 must
(a) permit the extraction of air from the cargo pump room bilges or from immediately above the transverse floor plates or bottom longitudinals;
(b) have an emergency intake that is
(i) situated in the ventilation ducts at a height of at least 2 m above the lower platform of the cargo pump room, and
(ii) fitted with a fire damper that is capable of being opened and closed from the weather deck or the lower platform of the cargo pump-room; and
(c) provide a means of ensuring a free flow of gases through the lower platform of the cargo pump-room to the ventilation duct intakes.
112 (1) In addition to the requirements of regulation 5.2, a vessel must be fitted with means to automatically shut down the ventilation fans for a space when a fixed gas fire-extinguishing system for that space is activated.
(2) In addition to the requirements of regulation 5.2.2.3, a vessel must be fitted with a means of control if the vessel is provided with any other equipment than that referred to in that regulation, including hydraulic power systems, that could contribute to sustaining a fire or create any other unsafe condition in the case of fire, in the space in which that other equipment is fitted.
113 (1) In addition to the restriction in regulation 5.3.1.1 on the use of combustible insulating materials, organic foam must not be used in the mail rooms or baggage rooms of a passenger vessel.
(2) If organic foam is used in a cargo space or a refrigerated compartment of a service space,
(a) the exposed surfaces of the foam must be
(i) sealed with an intumescent coating that meets the flame spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code, and
(ii) covered with a steel-sheet protective facing;
(b) in the case of organic foam used in a cargo space or a refrigerated compartment of a service space on a vessel of steel construction, the boundaries to the space must be of steel construction; and
(c) in the case of organic foam used in a refrigerated compartment of a service space on a vessel of aluminum construction, the boundaries to the space must be of steel or aluminum construction.
114 In addition to the requirements of regulation 6, plastic piping fitted on a vessel must meet the flame spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code and must be subject of a Minister’s type approval indicating that it meets the requirements set out in the IMO Resolution A.753(18), entitled Guidelines for the Application of Plastic Pipes on Ships.
115 In addition to the requirements of regulation 7.5, a smoke detector must be installed in every cabin and every service space, regardless of the method of fire protection chosen.
116 For the purposes of regulation 7.6, “where it is shown to the satisfaction of the Administration that the ship is engaged on voyages of such short duration that it would be unreasonable to apply this requirement” is to be read as “in the case of voyages of not more than 48 hours’ duration during which the cargo holds are opened to load or unload cargo”.
117 (1) Regulation 7.8.1 applies in respect of a vessel that is not a Safety Convention vessel only if it
(a) is carrying more than 50 passengers or more than 25 berthed passengers; or
(b) is carrying more than 100 unberthed passengers and is on a voyage during which it is more than 15 nautical miles from the point of departure or 5 nautical miles from shore.
(2) The fire patrols required by regulation 7.8.1 must be performed at least once every hour and must include a patrol of the entire vessel.
118 In addition to the requirements of regulation 7, every passenger vessel that is scheduled to be at a dock for more than one hour must, immediately on arrival at the dock, be connected to the shore fire-alarm system or to the local fire-station telephone system, if either system is fitted at the dock.
119 The class division requirements of regulation 9.2.3.4 for stairways that penetrate more than a single deck apply to any area, such as a landing or corridor, between the stairways, if those stairways provide continuous fire shelter as described in subsection 147(6).
120 (1) In addition to the requirements of regulation 9.4.1.1.2, every door in an “A” class division must meet the following requirements:
(a) the gap between the door leaf and its frame, as installed on board the vessel, must not exceed the gap measured when the door was tested in accordance with the FTP Code, but, in the case where the door was approved without a sill being part of the frame, the gap under the door, as installed on board the vessel, must not exceed the gap set out in regulation 9.4.1.1.2; and
(b) a grille or louvre must not be fitted in the door.
(2) The hose port requirements of regulation 9.4.1.1.8 apply in respect of every hose port fitted in a door in an “A” class division.
(3) If a ventilation duct passes through a main horizontal zone division on a passenger vessel, a fail-safe automatic-closing fire damper must be fitted in accordance with regulation 9.4.1.1.9, and the duct between the division and the damper must meet the requirements of that regulation.
(4) In addition to the requirements of regulations 9.4.1.1 and 9.4.1.2, every door in an “A” or “B” class division must be fitted with a thin metal identification plate that
(a) has clearly stamped on it the door manufacturer’s name, the “A” or “B” class rating, the type approval certificate number and the number of the drawing to which the door has been manufactured; and
(b) is screwed or riveted to either of the vertical edges of the door panel.
121 (1) In addition to the requirements of regulation 9.4.2.1, the following requirements must be met:
(a) the gap between every door leaf and its frame in an “A” class division, as installed on board the vessel, must not exceed the gap measured when the door was tested in accordance with the FTP Code, but, in the case where the door was approved without a sill being part of the frame, the gap under the door, as installed on board the vessel, must not exceed the gap set out in regulation 9.4.2.1 for an “A” class division;
(b) a grille or louvre must not be fitted in a door in an “A” class division; and
(c) every door in an “A” or “B” class division must be fitted with a thin metal identification plate that
(i) has clearly stamped on it the door manufacturer’s name, the “A” or “B” class rating, the type approval certificate number and the number of the drawing to which the door has been manufactured, and
(ii) is screwed or riveted to either of the vertical edges of the door panel.
(2) For the purposes of regulation 9.4.2.2, if hold-back arrangements fitted with remote-release devices of the fail-safe type are utilized,
(a) the arrangements must be capable of being operated at the door and from the wheelhouse; and
(b) a fire door open-close indicator panel must be provided in the wheelhouse.
122 In addition to the requirements of regulation 9.5.2.6, a vessel that has cargo pump-rooms must not be fitted with windows in the boundaries of those rooms.
123 (1) Despite regulation 9.7.2.1, the galley ventilation systems must, on all cargo vessels and all passenger vessels, be separate from the ventilation systems serving other spaces.
(2) The requirements of regulation 9.7.4.3 apply in respect of every stairway enclosure serving more than one deck on all cargo vessels and all passenger vessels.
124 Every pressure container for a fixed fire-extinguishing system required by Regulation 10 must bear a mark indicating that it
(a) meets the applicable requirements for transport by road or ship that are set out in section 5.10 of the Transportation of Dangerous Goods Regulations;
(b) meets the applicable requirements for transport by road or ship that are set out in Title 49, subpart C of part 178 of the Code of Federal Regulations of the United States; or
(c) meets the applicable requirements for transportable pressure equipment that are set out in Directive 2010/35/EU of the European Parliament and of the Council and has undergone a conformity assessment procedure in accordance with that Directive by a notified body designated by a member state of the European Union.
125 The pipes, valves and fittings used with the equipment required by regulation 10.2
(a) must be made of corrosion-resistant metal or galvanized steel; and
(b) must not be readily rendered ineffective at an anticipated low ambient temperature or by heat from a fire.
126 (1) If the fire main is an integral part of a fixed deck foam fire-extinguishing system with monitors, the isolating valves required by regulation 10.2.1.4.1 must be fitted immediately forward of each monitor.
(2) In addition to the isolating valves required by regulation 10.2.1.4.1, valves must be fitted to sections of the fire main that
(a) are subject to freezing;
(b) could be damaged because of a fire or explosion; or
(c) might not be required when any other part of the fire main is used.
(3) The valves required by subsection (2) must be
(a) operable from positions that are readily accessible
(b) protected from freezing, fire and explosions; and
(c) clearly marked.
(4) Every valve fitted to fire piping must be designed to open with a counter-clockwise rotation of the valve’s handle.
(5) The requirements of regulation 10.2.1.4.4 apply in respect of combination carriers.
127 Despite regulation 10.2.1.5.1, on a cargo vessel of less than 500 gross tonnage or on a passenger vessel of less than 500 gross tonnage that is not a Safety Convention vessel, the number and position of hydrants must be such that one jet of water can reach any part of the vessel.
128 (1) In addition to being provided with the hydrants required by regulation 10.2.1.5.1,
(a) a passenger vessel on a near coastal voyage, Class 1, or an unlimited voyage and a vessel of 500 gross tonnage or more must be provided, in each machinery space of category A, with one hydrant on the port side and one hydrant on the starboard side; and
(b) any other vessel of less than 500 gross tonnage must be provided with one hydrant in each machinery space of category A.
(2) A fire hose and nozzle must be fitted on each hydrant required by subsection (1).
(3) If the size or configuration of a machinery space of category A would render a hydrant required by subsection (1) ineffective, the hydrant must be located near the main access to the space.
(4) In addition to being provided with the hydrants required by regulation 10.2.1.5.1, a cargo vessel of 2 000 gross tonnage or more must
(a) be provided with a hydrant in the shaft tunnel, if any, adjacent to the engine room watertight door; and
(b) meet the requirements of regulation 10.2.1.5.2.2.
129 Every fire hydrant must be installed so that
(a) a fire hose can be easily connected to it;
(b) it is limited to a position from the horizontal to the vertical pointing downward, so that the fire hose will lead horizontally or downward in order to minimize the possibility of kinking; and
(c) there is sufficient clearance below it to accommodate the radius of bend of the fire hose under pressure and to allow deployment of the hose in every direction.
130 The international shore connection required by regulation 10.2.1.7 must be stored on the vessel so as to be readily accessible. A notice in English and French indicating the connection’s location and the maximum working pressure of the piping system must be posted on the vessel.
131 In addition to the requirements of regulation 10.2.2, the following requirements must be met in respect of a vessel’s fire pumps:
(a) if the vessel is fitted with two or more power-driven fire pumps, a non-return valve must be fitted to the discharge line of each pump to prevent water from backing through the pump when it is not operating;
(b) a power-driven fire pump must be self-priming and fitted with pressure gauges on their suction and discharge sides;
(c) a manual fire pump must be operable without the need for manual priming and must be capable of delivering a jet of water of at least 12 m from the nozzle;
(d) a fire pump’s sea connection must have arrangements to prevent blockage of the connection’s inlet by ice, slush and debris; and
(e) a fire pump must not have an impeller that can be damaged by heat from the pump or by the pump running dry.
132 If a bilge pump is used as a fire pump as permitted by regulation 10.2.2.1, the bilge pumping system and the fire pumping system must be capable of simultaneous operation.
133 (1) One of the fire pumps required by regulation 10.2.2.2 may be manually operated if the vessel is not a Safety Convention vessel, is of less than 1 000 gross tonnage and, in the case of a passenger vessel, is engaged on a sheltered waters voyage or a near coastal voyage, Class 2. If one of the fire pumps is manually operated and is located outside the space where the other fire pump required by that regulation and its source of power are located, the manually operated fire pump may also be used as an emergency fire pump if one is required by regulation 10.2.2.3.1.2.
(2) A power-driven fire pump that is required by regulation 10.2.2.2.2 to be on a vessel of less than 1 000 gross tonnage, but that is not required to be independently driven, must not be powered by a main engine unless the engine can be operated independently of the propeller shafting.
(3) Despite regulation 10.2.2.2.2 and subsection (1), if a cargo vessel to which that subsection applies is engaged on a sheltered waters voyage or a near coastal voyage, Class 2,
(a) only one independently driven fire pump is required in order to meet the requirements of that regulation, and it must be power-driven; and
(b) regulation 10.2.2.3.1.2 does not apply.
134 (1) For the purposes of regulation 10.2.2.4.2,
(a) “in any event be capable of delivering at least the two required jets of water” is to be read as “in normal operating conditions be capable of delivering at least the required jets of water”; and
(b) “at least the two jets of water required in paragraph 2.1.5.1” is to be read as “at least the required jets of water”.
(2) The fire pumps on vessels of less than 500 gross tonnage, other than passenger vessels that are Safety Convention vessels, are not required to meet the minimum capacity requirement of 25 m3/h set out in regulation 10.2.2.4.2.
135 (1) In addition to the requirements of regulation 10.2.3.1.1, the fire hoses in a machinery space of category A or that serve a space that contains flammable materials must be connected to the fire hydrants at all times. If there is more than one fire hose in a machinery space of category A, one of the fire hoses in that space must also be connected to a portable foam applicator.
(2) In addition to the requirements of regulation 10.2.3.1.1, every fire hose must be
(a) stowed in a space designed to permit the deployment of the hose without it becoming entangled; and
(b) stored in a fire hose cabinet that protects the hose from the anticipated low ambient temperatures.
(3) The nozzles, couplings and fittings for the fire hoses on a tanker must be made of brass, bronze or other equivalent non-sparking material.
(4) For the purposes of regulation 10.2.3.2.1,
(a) the design of the piping system must be taken into consideration in determining the number of fire hoses;
(b) the minimum diameter of a fire hose must be 38 mm; and
(c) every fire hose must have the same diameter, but hoses in machinery spaces and other interior locations may have a smaller diameter than hoses in other locations if the smaller diameter is for the purpose of convenient handling.
(5) For the purposes of regulation 10.2.3.3.3, if section 127 applies and the number and position of hydrants on the vessel is such that only one jet of water may reach any part of the vessel, “from two jets” is to be read as “from one jet”.
136 (1) For the purposes of regulation 10.3.2.1, on a passenger vessel
(a) each main vertical zone below the bulkhead deck must be provided with the greater of
(i) two portable water fire extinguishers of at least 9 L capacity each or two portable fire extinguishers of equivalent fire-extinguishing capability, and
(ii) two portable fire extinguishers of a type described in subparagraph (i) for each 15 m, or fraction of 15 m, in length of the zone;
(b) each main vertical zone on or above the bulkhead deck must be provided, on each side of the vessel, with one portable fire extinguisher of a type described in subparagraph (a)(i); and
(c) despite paragraph (b), if the vessel is of less than 500 gross tonnage and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2, each main vertical zone on or above the bulkhead deck must be provided with one portable fire extinguisher of a type described in subparagraph (a)(i).
(2) For the purposes of regulation 10.3.2.1, on a cargo vessel
(a) the area within the outside boundary of each accommodation space below the bulkhead deck must be provided with the greater of
(i) two portable water fire extinguishers of at least 9 L capacity each or two portable fire extinguishers of equivalent fire-extinguishing capability, and
(ii) two portable fire extinguishers of a type described in subparagraph (i) for each 15 m, or fraction of 15 m, in length of the area; and
(b) the area within the outside boundary of each accommodation space on or above the bulkhead deck must be provided with one portable fire extinguisher of a type described in subparagraph (a)(i) for each 15 m, or fraction of 15 m, in length of the area.
(3) For the purposes of regulation 10.3.2.1, in addition to the portable fire extinguishers required by subsections (1) and (2),
(a) one portable water fire extinguisher of at least 9 L capacity or one portable fire extinguisher of equivalent fire-extinguishing capability must be provided next to the access to each storeroom for each 232 m2, or fraction of 232 m2, of surface area of the storeroom;
(b) each galley and each pantry that contains cooking facilities must be provided with one portable dry-chemical fire extinguisher of at least 4.5 kg capacity or one portable fire extinguisher of equivalent fire-extinguishing capability for each 232 m2, or fraction of 232 m2, of surface area of the galley or pantry; and
(c) each control station must be provided with one portable fire extinguisher of a type described in paragraph (b).
137 (1) Every portable fire extinguisher must be fitted with a clamp bracket that
(a) is designed to withstand the roll, pitch and vibration of the vessel; and
(b) holds the fire extinguisher securely in place but provides quick and positive release of the fire extinguisher for immediate use.
(2) Every wheeled-type portable fire extinguisher must be fitted with a metal clip arrangement that
(a) is designed to withstand the roll, pitch and vibration of the vessel; and
(b) holds the fire extinguisher securely in place but provides quick and positive release of the fire extinguisher for immediate use.
138 Regulation 10.3.3 does not apply in respect of a vessel that is not a Safety Convention vessel and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
139 If a machinery space on a vessel that is constructed of wood, glass-reinforced plastic or aluminum alloy is provided with a fixed gas fire-extinguishing system, the system must, despite regulation 10.4.1.1.1, have a sufficient quantity of gas to provide two independent charges of gas.
140 (1) Regulations 10.5.1.2.1, 10.5.2.2.1 and 10.5.3.2.1 do not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
(2) The requirement in regulation 10.5.2.2.2 with respect to foam fire extinguishers of at least 45 L capacity each or equivalent does not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
(3) Regulation 10.5.6 does not apply in respect of a vessel that is not a Safety Convention vessel and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
141 For the purposes of regulation 10.6.3.2, the fire-extinguishing arrangements must include fixed gas fire-extinguishing systems, fixed foam fire-extinguishing systems and fixed pressure water-spraying fire-extinguishing systems that meet the applicable requirements of the FSS Code for the system.
142 For the purposes of regulation 10.7.1.2, “it is shown to the satisfaction of the Administration that a passenger ship is engaged on voyages of such short duration that it would be unreasonable to apply the requirements of paragraph 7.1.1” is to be read as “a passenger ship is engaged on voyages of not more than 48 hours’ duration during which the cargo holds are opened to discharge or receive cargo”.
143 (0.1) In addition to the requirements of regulation 10, firefighters’ outfits must meet any of the following:
(a) the applicable requirements of Directive 2014/90/EU of the European Parliament and of the Council of 23 July 2014 on marine equipment and repealing Council Directive 96/98/EC; or
(b) the applicable requirements of NFPA 1971, entitled Standard on Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting.
(0.2) In addition to the requirements of regulation 10, firefighters’ self-contained breathing apparatus must be rated for use in fighting fires and must meet any of the following:
(a) the applicable requirements of Directive 2014/90/EU of the European Parliament and of the Council of 23 July 2014 on marine equipment and repealing Council Directive 96/98/EC;
(b) the applicable requirements of NFPA 1981, entitled Standard on Open-Circuit Self-Contained Breathing Apparatus (SCBA) for Emergency Services; or
(c) the applicable requirements of Title 42, chapter I, subchapter G, part 84 of the Code of Federal Regulations of the United States, entitled Approval of Respiratory Protective Devices.
(1) Regulations 10.10.2.1 and 10.10.2.2 do not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and, if the vessel is not a cargo vessel, is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
(2) Regulation 10.10.2.3 applies only in respect of tankers of 500 gross tonnage or more.
144 (1) In addition to the requirements of regulation 10, a passenger vessel on a near coastal voyage, Class 1, or an unlimited voyage must be provided with the greater of
(a) three fire axes, and
(b) one fire axe for each 15 m, or fraction of 15 m, in length of the vessel.
(2) In addition to the requirements of regulation 10, a passenger vessel on a sheltered waters voyage or a near coastal voyage, Class 2, must be provided with
(a) if the vessel is of less than 500 gross tonnage but of 24 m or more in length, two fire axes; and
(b) if the vessel is of 500 gross tonnage or more, one fire axe for each 15 m, or fraction of 15 m, in length of the vessel.
(3) In addition to the requirements of regulation 10, a cargo vessel must be provided with
(a) if the vessel is of less than 500 gross tonnage but of 24 m or more in length, two fire axes; and
(b) if the vessel is of 500 gross tonnage or more, three fire axes.
145 (1) The public address system or other means of communication required by regulation 12.3 must be available on all cargo vessels and all passenger vessels throughout the spaces referred to in that regulation, the muster stations, the embarkation stations and the machinery spaces.
(2) Regulation 12.3 and subsection (1) do not apply before the first anniversary of the day on which this section comes into force.
146 (1) The crew accommodation areas of every passenger vessel must meet the requirements of regulation 13.3.2.5.1.
(2) Each escape hatch must be painted orange and be operable from both sides of the hatch.
147 (1) Every cargo vessel must meet the requirements of regulation 13.3.2.5.1, and the crew accommodation areas of the vessel must also meet those requirements.
(2) Each escape hatch must be painted orange and be operable from both sides of the hatch.
(3) Every cargo vessel must meet the requirements of regulation 13.3.2.6.2.
(4) The means of escape required by regulation 13.3.3.1 must be separated from one another so as to minimize the possibility of their being blocked at the same time as a result of an incident.
(5) Each means of escape required by regulation 13.3.3.2 must give direct access to another means of escape on the deck above.
(6) On a cargo vessel of 500 gross tonnage or more, if one of the means of escape required by regulation 13.3.3.2 or 13.3.3.3 from a restricted space or group of spaces connects more than two decks, one of those means must, if feasible, be a readily accessible stairway enclosure that provides continuous fire shelter from the space or group of spaces to the closest lifeboat and life-raft embarkation deck. If the stairway enclosure that provides continuous fire shelter is not feasible, an escape route from the restricted space or group of spaces to the embarkation deck must be provided. The entire length of the escape route must be protected from the fire by “A” class divisions.
(7) Despite regulation 13.3.3.2, if installing a stairway or trunk is not feasible, a vertical ladder may be used as the second means of escape from crew spaces that are entered only occasionally.
(8) Despite regulation 13.3.3.3, if installing a stairway is not feasible, a vertical ladder may be used as one of the means of escape from crew spaces that are entered only occasionally.
148 Regulation 13.4.3 does not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
149 Any words included in the symbols required by regulation 13.7.1.1 to mark the escape routes must be printed in English and French.
150 (1) All cargo vessels and all passenger vessels must display “mimic” plans in accordance with regulation 13.7.2.2 and must display those plans in every space occupied by the crew.
(2) Any words on the “mimic” plans must be printed in English and French.
151 If a vessel is fitted with a fixed gas fire-extinguishing system, the instructions on firefighting activities and firefighting procedures required by regulation 15.2.3.4.2 must include instructions on the use of firefighters’ outfits, including breathing apparatus, and the protected space re-entry procedure recommended by the manufacturer of the system.
152 The fire control plans and booklets required by regulation 15.2.4 must be
(a) in the working language of the vessel; and
(b) in English or French, or in both languages, according to the needs of the shoreside firefighting personnel.
153 Despite section 102, regulations 15.2.1, 15.2.2 and 15.3.1 do not apply in respect of vessels to which the Fire and Boat Drills Regulations apply.
154 An engineering analysis submitted under regulation 17.3 must be written in English or French.
155 The “NO SMOKING” signs required by regulation 18.7.10 must be in English and French as well as in the working language of the vessel.
156 The operations manual required by regulation 18.8.1 must be in the working language of the vessel.
157 The requirements of regulation 20.5 apply in respect of all passenger vessels.
158 (1) If a water curtain is part of a fixed fire-extinguishing system referred to in regulation 20.6.1, a strip that is 900 mm wide must be painted on the deck under the water curtain and be marked with the words “TO BE KEPT CLEAR OF VEHICLES AT ALL TIMES” and “LAISSER CET ESPACE LIBRE DE VÉHICULES EN TOUT TEMPS”.
(2) Each portable fire extinguisher required by regulation 20.6.2.1 must be a portable dry-chemical fire extinguisher of at least 4.5 kg capacity or a portable fire extinguisher of equivalent fire-extinguishing capability.
(3) In the case of a vessel that is not a Safety Convention vessel and that is engaged on a sheltered waters voyage or a near coastal voyage, Class 2, the reference in regulation 20.6.2.2.1 to “three water-fog applicators” is to be read as a reference to “one water-fog applicator”.
159 Regulations 21, 22 and 23 do not apply in respect of a vessel that is not a Safety Convention vessel and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.
200 The following definitions apply in this Part.
A-60 class fire rating means the thermal and integrity requirements specified for “A-60” class divisions. (indice de résistance au feu de type A-60)
“F” class divisions means divisions that are formed by bulkheads, decks, ceilings or linings and that meet the fire-test requirements for “F” class divisions set out in Annex 1 to the FTP Code. (cloisonnements du type « F »)
201 (1) This Part applies in respect of Canadian vessels everywhere that are
(a) passengers vessels of 24 m or more in length that
(i) are not Safety Convention vessels,
(ii) are carrying no berthed passengers and fewer than 100 unberthed passengers, and
(iii) are engaged on a sheltered waters voyage or a near coastal voyage, Class 2, limited; or
(b) cargo vessels of 24 m or more in length but of less than 500 gross tonnage.
(2) This Part does not apply in respect of
(a) vessels that carry dangerous goods, other than in limited quantities, and that are referred to in regulation 19.2.2 of Chapter II-2 of SOLAS or have cargo spaces referred to in that regulation;
(b) pleasure craft;
(c) fishing vessels;
(d) high-speed craft;
(e) vessels that do not have mechanical means of propulsion;
(f) wooden vessels of primitive build;
(g) vessels that are capable of engaging in the drilling for, or the production, conservation or processing of, oil or gas; or
(h) nuclear vessels.
202 Except as otherwise provided in this Part, a vessel’s authorized representative must ensure that the requirements of sections 205 to 234 are met in respect of the vessel.
203 (1) If a vessel that was constructed before the day on which this section comes into force held, at any time before that day, a certificate issued under the Vessel Certificates Regulations or under section 318 or 319 of the Canada Shipping Act, R.S.C., 1985, c. S-9, its authorized representative may ensure that the requirements with respect to structural fire protection that would have been required under the Act to be met, on the day before that day, are met instead of the requirements of sections 205 to 234 of these Regulations.
(2) For the purposes of subsection (1), the reference to section 318 or 319 of the Canada Shipping Act, R.S.C., 1985, c. S-9, includes any predecessor enactment relating to the same subject matter.
204 (1) Section 203 does not apply in respect of
(a) parts of a vessel that, beginning on the day on which this section comes into force, undergo repairs, alterations or modifications that
(i) substantially alter the vessel’s dimensions or its passenger accommodation spaces, or
(ii) substantially increase the vessel’s service life or the life of the vessel’s outfitting; or
(b) parts of a vessel that, beginning on the day on which this section comes into force, are replaced.
(2) Section 203 does not apply if the vessel’s intended service changes in such a manner that any of the requirements with respect to structural fire protection that would have been required under the Act to be met are no longer met.
205 (1) On a vessel whose hull is constructed of non-combustible materials,
(a) a deck or bulkhead that separates a machinery space from an accommodation space, service space or control station must
(i) consist of “A-15” class divisions, if the vessel is a passenger vessel, or of “A-0” class divisions, if the vessel is a cargo vessel, or
(ii) consist of “A-60” class divisions, if the machinery space is of category A and is not fitted with a fixed fire-extinguishing system; and
(b) a deck or bulkhead that separates a control station from an accommodation space or service space must consist of “B-15” class divisions.
(2) On a vessel whose hull is constructed of non-combustible materials, if a deck or boundary bulkhead contains an emergency source of power or if a deck or bulkhead separates a galley, paint-room, lamp-room or storeroom that contains highly flammable materials from an accommodation space, service space or control station, the deck or bulkhead must consist of
(a) “A-15” class divisions; or
(b) “B-15” class divisions, in the case of a galley in which any ovens, hot water appliances or other appliances are heated only by electricity.
206 (1) On a vessel whose hull is constructed of combustible materials,
(a) a deck or bulkhead that separates a machinery space from an accommodation space, service space or control station must consist of “F” class divisions or of “B-15” class divisions;
(b) a deck or bulkhead that separates a control station from an accommodation space or service space must consist of “F” class divisions; and
(c) the machinery space boundaries must, to the extent feasible, prevent the passage of smoke.
(2) On a vessel whose hull is constructed of combustible materials, if a deck or boundary bulkhead contains an emergency source of power or if a deck or bulkhead separates a galley, paint-room, lamp-room or storeroom that contains highly flammable materials from an accommodation space, service space or control station, the deck or bulkhead must consist of “F” class divisions or of “B-15” class divisions.
207 (1) On a vessel whose hull is constructed of non-combustible materials, the bulkhead of a corridor that serves an accommodation space, service space or control station must consist of “B-0” class divisions.
(2) On a vessel whose hull is constructed of combustible materials, the bulkhead of a corridor that serves an accommodation space, service space or control station must consist of “F” class divisions or of “B-0” class divisions.
(3) The bulkhead of a corridor that serves an accommodation space, service space or central control station must extend from deck to deck unless a continuous ceiling of the same class division as the bulkhead is fitted on both sides of the bulkhead, in which case the bulkhead may terminate at the continuous ceiling.
208 For the purposes of sections 205 to 207,
(a) “A” class divisions may be used instead of “B-15” class divisions or “F” class divisions;
(b) “A-15”, “A-30” or “A-60” class divisions may be used instead of “A-0” class divisions;
(c) “A-30” or “A-60” class divisions may be used instead of “A-15” class divisions; and
(d) “B-15” class divisions may be used instead of “B-0” class divisions.
209 The fire integrity of the divisions required by sections 205 to 207 must not be impaired by the passage of electrical cables, pipes, trunks, ducts or other transit devices through the divisions.
210 (1) An interior stairway that serves an accommodation space, service space or control station must be constructed of steel or other equivalent material.
(2) On a vessel whose hull is constructed of non-combustible materials, an interior stairway that connects more than two decks must be within an enclosure constructed of “B-15” class divisions.
(3) On a vessel whose hull is constructed of combustible materials, an interior stairway that connects more than two decks must be within an enclosure constructed of “F” class divisions.
211 A lift trunk that passes through an accommodation space or service space must be constructed of steel or other equivalent material and must be provided with a means of closing that permits control of drafts and smoke.
212 (1) The following doors and other closures of openings must have fire-resistant properties equivalent to those of the class divisions of the structures in which they are fitted:
(a) doors in an engine or boiler casing;
(b) doors and other closures of openings in a deck or bulkhead referred to in sections 205 to 207; and
(c) doors in an enclosure referred to in subsection 210(2) or (3).
(2) The doors to machinery spaces of category A must be self-closing and reasonably gastight.
(3) A door required by subsection (1) that is in an “A” class division must be reasonably gastight.
(4) Every door in an “A” class division must overlap the door frame, and allow for a gap, between the edges of the door and the top, bottom and sides of the door frame, that is the minimum needed to open and close the door.
(5) A grille or louvre must not be fitted in a door required by subsection (1) that is in an “A” class division.
(6) A hose port that is fitted in a door required by subsection (1) that is in an “A” class division must
(a) be self-closing;
(b) be constructed of material that has fire-resistance that is at least equivalent to the door in which it is fitted;
(c) have a clear opening that has a width and length of 150 mm when the door is closed; and
(d) be inset into the lower edge of the door, either on the side opposite the door hinges or, in the case of a sliding door, on the side nearest the opening.
(7) Every door required by subsection (1) that is in an “A” or “B” class division must be fitted with a thin metal identification plate that
(a) has clearly stamped on it the door manufacturer’s name, the “A” or “B” class rating, the type approval certificate number and the number of the drawing to which the door has been manufactured; and
(b) is screwed or riveted to either of the vertical edges of the door panel.
213 (1) If a skylight in a machinery space can be opened, the skylight must be capable of being closed from outside the space.
(2) Glass, acrylic or any other similar material must not be fitted in machinery space boundaries. However, wire-reinforced glass may be fitted in skylights and fire-rated glass may be fitted in windows in control rooms within machinery spaces.
(3) A skylight that is in a machinery space and contains wire-reinforced glass must be fitted with permanently attached external shutters of steel or other equivalent material.
214 Air spaces enclosed behind ceilings, panelling or linings in accommodation spaces, service spaces or control stations must be divided by close-fitting draft stops spaced not more than 7 m apart.
215 (1) Insulating materials must be non-combustible, except in a cargo space, mail room, baggage room, or refrigerated compartment of a service space. However, vapour barriers and adhesives used with insulating materials, as well as the insulating materials used for pipe fittings for cold service systems, need not be of non-combustible materials if the non-combustible materials are the minimum quantity feasible and their exposed surfaces have low flame spread characteristics.
(2) The exposed surface of insulating materials fitted on the internal boundaries of machinery spaces of category A must be impervious to oil and oil vapours.
216 If organic foam is used in a cargo space or a refrigerated compartment of a service space,
(a) the exposed surfaces of the foam must be
(i) sealed with an intumescent coating that meets the flame spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code, and
(ii) covered with a steel-sheet protective facing;
(b) in the case of organic foam used in a cargo space or a refrigerated compartment of a service space on a vessel of steel construction, the boundaries to the space must be of steel construction; and
(c) in the case of organic foam used in a refrigerated compartment of a service space on a vessel of aluminum construction, the boundaries to the space must be of steel or aluminum construction.
217 (1) Means must be provided for closing the main inlets and outlets of every ventilation system from a position outside the space served by the system. The means of closing must
(a) be readily accessible;
(b) be prominently and permanently marked as being the main inlet or outlet to the space; and
(c) indicate whether the inlets and outlets are open or closed.
(2) Power ventilation of accommodation spaces, service spaces, cargo spaces, control stations and machinery spaces must be capable of being stopped from a readily accessible position outside the space or station served. Access to this position must not be easily cut off in the event of a fire in the space served.
(3) Means of control must be provided for stopping ventilation fans. The means must
(a) if they are provided for stopping the ventilation serving machinery spaces, be grouped so as to be operable from two positions, one of which is outside those spaces; and
(b) if they are provided for stopping the ventilation of the machinery spaces, be entirely separate from the means provided for stopping the ventilation of other spaces.
(4) The means of control that are required by subsection (3) to be located outside the machinery spaces must be arranged so that a source of power to stop the fans and close the main openings is provided
(a) from each individual motor control circuit; or
(b) from a dedicated source of power feeding an individual motor, or a group of motors connected to a motor control centre for a particular space, without any shunt-trip arrangements.
(5) A stop circuit of the means of control referred to in subsection (4) that is activated manually must be manually reset.
(6) Means must be provided for closing, from a safe position, the annular spaces around funnels.
218 (1) A ventilation opening must not be installed in or under a stairway enclosure door.
(2) Any ventilation opening in a door in a corridor bulkhead must be in the lower half of the door and must be fitted with a grille made of non-combustible material.
(3) The total net area of a ventilation opening in or under a door in a corridor bulkhead must not be more than 0.05 m2.
219 (1) A ventilation duct that serves a machinery space of category A or a