    10 CFR § 429.43 — § 429.43 Commercial heating, ventilating, air conditioning (HVAC) equipment.

    Beta. Legal information, not legal advice. LEGALDIGM is not a law firm. Check the official source for the current text.

    Analyze this law with AI
    § 429.43 Commercial heating, ventilating, air conditioning (HVAC) equipment. (a) Determination of represented values. Manufacturers must determine the represented values, which include the certified ratings, for each basic model of commercial HVAC equipment either by testing, in conjunction with the applicable sampling provisions, or by applying an AEDM. (1) Units to be tested. (i) If the represented value is determined through testing, the general requirements of § 429.11 are applicable; and (ii) For each basic model selected for testing, a sample of sufficient size shall be randomly selected and tested to ensure that— (A) Any represented value of energy consumption or other measure of energy use of a basic model, or of a tested combination for variable refrigerant flow multi-split air conditioners and heat pumps certified to standards in terms of IEER as provided at paragraph (a)(3)(ii)(C) of this section, for which consumers would favor lower values shall be greater than or equal to the higher of: ( 1 ) The mean of the sample, where: And, x is the sample mean; n is the number of samples; and x i is the i th sample; or, ( 2 ) The upper 95 percent confidence limit (UCL) of the true mean divided by 1.05, where: And x is the sample mean; s is the sample standard deviation; n is the number of samples; and t 0.95 is the t statistic for a 95% one-tailed confidence interval with n-1 degrees of freedom (from Appendix A to subpart B of part 429). And, (B) Any represented value of energy efficiency or other measure of energy consumption of a basic model, or of a tested combination for variable refrigerant flow multi-split air conditioners and heat pumps certified to standards in terms of IEER as provided at paragraph (a)(3)(ii)(C) of this section, for which consumers would favor higher values shall be less than or equal to the lower of: ( 1 ) The mean of the sample, where: And, x is the sample mean; n is the number of samples; and x i is the i th sample; or, ( 2 ) The lower 95 percent confidence limit (LCL) of the true mean divided by 0.95, where: And x is the sample mean; s is the sample standard deviation; n is the number of samples; and t 0.95 is the t statistic for a 95% one-tailed confidence interval with n-1 degrees of freedom (from Appendix A to subpart B of part 429). (iii) For packaged terminal air conditioners and packaged terminal heat pumps, the represented value of cooling capacity shall be the average of the capacities measured for the sample selected as described in (a)(1)(ii) of this section, rounded to the nearest 100 Btu/h. (2) Alternative efficiency determination methods. (i) In lieu of testing, a represented value of efficiency or consumption for a basic model of commercial HVAC equipment must be determined through the application of an AEDM pursuant to the requirements of § 429.70 and the provisions of this section, where: (A) Any represented value of energy consumption or other measure of energy use of a basic model for which consumers would favor lower values shall be greater than or equal to the output of the AEDM and less than or equal to the Federal standard for that basic model; and (B) Any represented value of energy efficiency or other measure of energy consumption of a basic model for which consumers would favor higher values shall be less than or equal to the output of the AEDM and greater than or equal to the Federal standard for that basic model. (ii) [Reserved] (3) Product-specific provisions for determination of represented values. (i) Direct-expansion-dedicated outdoor air systems (DX-DOASes): (A) Individual model selection: ( 1 ) Representations for a basic model must be based on the least efficient individual model(s) distributed in commerce among all otherwise comparable model groups comprising the basic model, considering only individual models as provided in paragraph (a)(3)(i)(A)( 2 ) of this section. For the purpose of this paragraph (a)(3), an “otherwise comparable model group” means a group of individual models distributed in commerce within the basic model that do not differ in components that affect energy consumption as measured according to the applicable test procedure specified at 10 CFR 431.96 other than those listed in table 1 to paragraph (a)(3)(i)(A) of this section. An otherwise comparable model group may include individual models distributed in commerce with any combination of the components listed in table 1 (or none of the components listed in table 1). An otherwise comparable model group may consist of only one individual model. ( 2 ) For a basic model that includes individual models distributed in commerce with components listed in table 1 to paragraph (a)(3)(i)(A) of this section, the requirements for determining representations apply only to the individual model(s) of a specific otherwise comparable model group distributed in commerce with the least number (which could be zero) of components listed in table 1 included in individual models of the group. Testing under this paragraph shall be consistent with any component-specific test provisions specified in section 2.2.2 of appendix B to subpart F of part 431. Table 1 to Paragraph ( a )(3)( i )(A) Component Description Furnaces and Steam/Hydronic Heat Coils Furnaces and steam/hydronic heat coils used to provide primary or supplementary heating. Ducted Condenser Fans A condenser fan/motor assembly designed for optional external ducting of condenser air that provides greater pressure rise and has a higher rated motor horsepower than the condenser fan provided as a standard component with the equipment. Sound Traps/Sound Attenuators An assembly of structures through which the supply air passes before leaving the equipment or through which the return air from the building passes immediately after entering the equipment, for which the sound insertion loss is at least 6 dB for the 125 Hz octave band frequency range. VERS Preheat Electric resistance, hydronic, or steam heating coils used for preheating outdoor air entering a VERS. (B) When certifying, the following provisions apply. ( 1 ) For ratings based on tested samples, the represented value of moisture removal capacity shall be between 95 and 100 percent of the mean of the moisture removal capacities measured for the units in the sample selected, as described in paragraph (a)(1)(ii) of this section, rounded to the nearest lb/hr multiple specified in table 2 to paragraph (a)(3)(i)(B) of this section. ( 2 ) For ratings based on an AEDM, the represented value of moisture removal capacity shall be the moisture removal capacity output simulated by the AEDM, as described in paragraph (a)(2) of this section, rounded to the nearest lb/hr multiple specified in table 2 to paragraph (a)(3)(i)(B) of this section. Table 2 Paragraph ( a )(3)( i )(B)—Rounding Requirements for Rated Moisture Removal Capacity Moisture removal capacity (MRC), lb/hr Rounding multiples, lb/hr 0 < MRC ≤ 30 0.2 30 < MRC ≤ 60 0.5 60 < MRC ≤ 180 1 180 < MRC 2 (ii) Variable refrigerant flow multi-split air conditioners and heat pumps (other than air-cooled with cooling capacity less than 65,000 btu/h). When certifying to standards in terms of IEER, the following provisions apply. (A) Outdoor Unit Model Selection. All representations for basic models of VRF multi-split systems must be based on the least-efficient outdoor unit model(s) distributed in commerce within the basic model. (B) Indoor Unit Model Selection. A manufacturer must determine represented values for basic models of VRF multi-split systems based on the following provisions regarding selection of indoor units: ( 1 ) The combination of indoor unit models shall be selected per the certified tested combination in the STI, subject to the provisions in paragraph (a)(3)(ii)(B)( 2 ) of this section. ( 2 ) For each indoor unit model identified in the tested combination for which the model number certified in the STI does not fully specify the presence or absence of all components, a fully-specified indoor unit model shall be selected that meets the following qualifications: ( i ) Is distributed in commerce; and ( ii ) Has a model number consistent with the certified indoor unit model number ( i.e., shares all digits of the model number that are specified in the certified indoor unit model number); and ( iii ) Among the group of all indoor models meeting the criteria from paragraphs (a)(3)(ii)(B)( 2 )( i ) and ( ii ) of this section, has the least number (which could be zero) of components listed in Table 2 to paragraph (a)(3)(ii)(B)( 2 ) of this section. Table 3 to Paragraph ( a )(3)( ii )(B)( 2 )—Specific Components for Variable Refrigerant Flow Multi-Split Systems Component Description Air economizers An automatic system that enables a cooling system to supply and use outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather. Dehumidification Components An assembly that reduced the moisture content of the supply air through moisture transfer with solid or liquid desiccants. (C) Represented Values for Different Indoor Unit Combinations. ( 1 ) If a basic model includes only one type of indoor unit combination ( i.e., ducted, non-ducted, or SDHV), a manufacturer must determine the represented values for the basic model in accordance with the sampling plan set forth in § 429.11 and paragraph (a)(1) of this section if the represented values are determined through testing, or in accordance with the provisions for applying an AEDM set forth in paragraph (a)(2) of this section and § 429.70. Indoor unit models must be selected in accordance with paragraph (a)(3)(ii)(B) of this section. ( 2 ) If a basic model includes more than one type of indoor unit combination ( i.e., ducted, non-ducted, and/or SDHV): ( i ) A manufacturer must determine separate represented values for each type of indoor unit combination. If the represented values are determined through testing, a manufacturer must test, at a minimum, a single tested combination that represents each type of indoor unit combination included in that basic model. A manufacturer may alternatively determine separate represented values through application of an AEDM as set forth in paragraph (a)(2) of this section and § 429.70. Indoor unit models within the indoor unit combination must be selected in accordance with paragraph (a)(3)(ii)(B) of this section. ( ii ) A manufacturer may also determine optional “mixed” representations by calculating the mean value across any two required representations described in the paragraph (a)(3)(ii)(C)( 2 )( i ) of this section ( i.e., a representation for “mixed ducted/non-ducted” would be determined by averaging the ducted representation and the non-ducted representation; a representation for “mixed ducted/SDHV” would be determined by averaging the ducted representation and the SDHV representation, and a representation for “mixed non-ducted/SDHV” would be determined by averaging the non-ducted representation and the SDHV representation). (iii) Single package vertical units. When certifying to standards in terms of IEER, the following provisions apply. (A) For individual model selection: ( 1 ) Representations for a basic model must be based on the least efficient individual model(s) distributed in commerce among all otherwise comparable model groups comprising the basic model, except as provided in paragraph (a)(3)(iii)(A)( 2 ) of this section for individual models that include components listed in table 4 to this paragraph (a)(3)(iii)(A). For the purpose of this paragraph (a)(3)(iii)(A)( 1 ), “otherwise comparable model group” means a group of individual models distributed in commerce within the basic model that do not differ in components that affect energy consumption as measured according to the applicable test procedure specified at 10 CFR 431.96 other than those listed in table 4 to this paragraph (a)(3)(iii)(A). An otherwise comparable model group may include individual models distributed in commerce with any combination of the components listed in table 4 (or none of the components listed in table 4). An otherwise comparable model group may consist of only one individual model. ( 2 ) For a basic model that includes individual models distributed in commerce with components listed in table 4 to this paragraph (a)(3)(iii)(A), the requirements for determining representations apply only to the individual model(s) of a specific otherwise comparable model group distributed in commerce with the least number (which could be zero) of components listed in table 4 included in individual models of the group. Testing under this paragraph (a)(3)(iii)(A)( 2 ) shall be consistent with any component-specific test provisions specified in section 4 of appendix G1 to subpart F of 10 CFR part 431. Table 4 to Paragraph ( a )(3)( iii )(A)—Specific Components for Single Package Vertical Units Component Description Desiccant Dehumidification Components An assembly that reduces the moisture content of the supply air through moisture transfer with solid or liquid desiccants. Air Economizers An automatic system that enables a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mid or cold weather. Ventilation Energy Recovery System (VERS) An assembly that preconditions outdoor air entering the equipment through direct or indirect thermal and/or moisture exchange with the exhaust air, which is defined as the building air being exhausted to the outside from the equipment. Steam/Hydronic Heat Coils Coils used to provide supplemental heating. Hot Gas Reheat A heat exchanger located downstream of the indoor coil that heats the Supply Air during cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to Cooling Capacity provided by the equipment. Fire/Smoke/Isolation Dampers A damper assembly including means to open and close the damper mounted at the supply or return duct opening of the equipment. Powered Exhaust/Powered Return Air Fans A powered exhaust fan is a fan that transfers directly to the outside a portion of the building air that is returning to the unit, rather than allowing it to recirculate to the indoor coil and back to the building. A powered return fan is a fan that draws building air into the equipment. Sound Traps/Sound Attenuators An assembly of structures through which the supply air passes before leaving the equipment or through which the return air from the building passes immediately after entering the equipment for which the sound insertion loss is at least 6 dB for the 125 Hz octave band frequency range. Hot Gas Bypass A method to adjust the cooling delivered by the equipment in which some portion of the hot high-pressure refrigerant from the discharge of the compressor(s) is diverted from its normal flow to the outdoor coil and is instead allowed to enter the indoor coil to modulate the capacity of a refrigeration circuit or to prevent evaporator coil freezing. (B) The represented value of cooling capacity must be between 95 percent and 100 percent of the mean of the capacities measured for the units in the sample selected as described in paragraph (a)(1)(ii) of this section, or between 95 percent and 100 percent of the net sensible cooling capacity output simulated by the alternative energy-efficiency determination method (AEDM) as described in paragraph (a)(2) of this section. (C) Represented values must be based on performance (either through testing or by applying an AEDM) of individual models with components and features that are selected in accordance with section 4 of appendix G1 to subpart F of 10 CFR part 431. (iv) Computer room air conditioners. When certifying to standards in terms of net sensible coefficient of performance (NSenCOP), the following provisions apply. (A) For individual model selection: ( 1 ) Representations for a basic model must be based on the least-efficient individual model(s) distributed in commerce among all otherwise comparable model groups comprising the basic model, except as provided in paragraph (a)(3)(iv)(A)( 2 ) of this section for individual models that include components listed in table 5 to paragraph (a)(3)(iv)(A) of this section. For the purpose of this paragraph (a)(3)(iv)(A)( 1 ), otherwise comparable model group means a group of individual models distributed in commerce within the basic model that do not differ in components that affect energy consumption as measured according to the applicable test procedure specified at 10 CFR 431.96 other than those listed in table 5 to paragraph (a)(3)(iv)(A) of this section. An otherwise comparable model group may include individual models distributed in commerce with any combination of the components listed in table 5 (or none of the components listed in table 5). An otherwise comparable model group may consist of only one individual model. ( 2 ) For a basic model that includes individual models distributed in commerce, with components listed in table 5 to paragraph (a)(3)(iv)(A) of this section, the requirements for determining representations apply only to the individual model(s) of a specific otherwise comparable model group distributed in commerce with the least number (which could be zero) of components listed in table 5 to paragraph (a)(3)(iv)(A) included in individual models of the group. Testing under this paragraph (a)(3)(iv)(A)( 2 ) shall be consistent with any component-specific test provisions specified in section 4 of appendix E1 to subpart F of 10 CFR part 431. Table 5 to Paragraph (a)(3)(iv)(A) —Specific Components for Computer Room Air Conditioners Component Description Air Economizers An automatic system that enables a cooling system to supply and use outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather. Process Heat Recovery/Reclaim Coils/Thermal Storage A heat exchanger located inside the unit that conditions the equipment's supply air using energy transferred from an external source using a vapor, gas, or liquid. Evaporative Pre-cooling of Air-cooled Condenser Intake Air Water is evaporated into the air entering the air-cooled condenser to lower the dry-bulb temperature and thereby increase efficiency of the refrigeration cycle. Steam/Hydronic Heat Coils Coils used to provide supplemental heat. Refrigerant Reheat Coils A heat exchanger located downstream of the indoor coil that heats the supply air during cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to cooling capacity provided by the equipment. Powered Exhaust/Powered Return Air Fans A powered exhaust fan is a fan that transfers directly to the outside a portion of the building air that is returning to the unit, rather than allowing it to recirculate to the indoor coil and back to the building. A powered return air fan is a fan that draws building air into the equipment. Compressor Variable Frequency Drive (VFD) A device connected electrically between the equipment's power supply connection and the compressor that can vary the frequency of power supplied to the compressor in order to allow variation of the compressor's rotational speed. If the manufacturer chooses to make representations for performance at part-load and/or low-ambient conditions, compressor VFDs must be treated consistently for all cooling capacity tests for the basic model ( i.e., if the compressor VFD is installed and active for the part-load and/or low-ambient tests, it must also be installed and active for the NSenCOP test). Fire/Smoke/Isolation Dampers A damper assembly including means to open and close the damper mounted at the supply or return duct opening of the equipment. Non-Standard Indoor Fan Motors The standard indoor fan motor is the motor specified in the manufacturer's installation instructions for testing and shall be distributed in commerce as part of a particular model. A non-standard motor is an indoor fan motor that is not the standard indoor fan motor and that is distributed in commerce as part of an individual model within the same basic model. For a non-standard indoor fan motor(s) to be considered a specific component for a basic model (and thus subject to the provisions of paragraph (a)(3)(iv)(A) of this section), the following provisions must be met: 1. Non-standard indoor fan motor(s) must meet the minimum allowable efficiency determined per section D.2.1 of AHRI 1360-2022 (incorporated by reference, see § 429.4) ( i.e., for non-standard indoor fan motors) or per section D.2.2 of AHRI 1360-2022 for non-standard indoor integrated fan and motor combinations). If the standard indoor fan motor can vary fan speed through control system adjustment of motor speed, all non-standard indoor fan motors must also allow speed control (including with the use of VFD). Humidifiers A device placed in the supply air stream for moisture evaporation and distribution. The device may require building steam or water, hot water, electricity, or gas to operate. Flooded Condenser Head Pressure Controls An assembly, including a receiver and head pressure control valve, used to allow for unit operation at lower outdoor ambient temperatures than the standard operating control system. Chilled Water Dual Cooling Coils A secondary chilled water coil added in the indoor air stream for use as the primary or secondary cooling circuit in conjunction with a separate chiller. Condensate Pump A device used to pump condensate and/or humidifier drain water from inside the unit to a customer drain outside the unit. (B) The represented value of net sensible cooling capacity must be between 95 percent and 100 percent of the mean of the capacities measured for the units in the sample selected as described in paragraph (a)(1)(ii) of this section, or between 95 percent and 100 percent of the net sensible cooling capacity output simulated by the AEDM as described in paragraph (a)(2) of this section. (v) Water-Source Heat Pumps. When certifying to standards in terms of IEER and ACOP, the following provisions apply. (A) Individual model selection: (1) Representations for a basic model must be based on the least efficient individual model(s) distributed in commerce among all otherwise comparable model groups comprising the basic model, except as provided in paragraph (a)(3)(v)(A)( 2 ) of this section for individual models that include components listed in table 6 to paragraph (a)(3)(v)(A) of this section. For the purpose of this paragraph (a)(3)(v)(A)( 1 ), “otherwise comparable model group” means a group of individual models distributed in commerce within the basic model that do not differ in components that affect energy consumption as measured according to the applicable test procedure specified at 10 CFR 431.96 other than those listed in table 6 to paragraph (a)(3)(v)(A) of this section. An otherwise comparable model group may include individual models distributed in commerce with any combination of the components listed in table 6 (or none of the components listed in table 6) to paragraph (a)(3)(v)(A) of this section. An otherwise comparable model group may consist of only one individual model. (2) For a basic model that includes individual models distributed in commerce with components listed in table 6 to paragraph (a)(3)(v)(A) of this section, the requirements for determining representations apply only to the individual model(s) of a specific otherwise comparable model group distributed in commerce with the least number (which could be zero) of components listed in table 6 to paragraph (a)(3)(v)(A) of this section included in individual models of the group. Testing under this paragraph shall be consistent with any component-specific test provisions specified in section 3 of appendix C1 to subpart F of 10 CFR part 431. Table 6 to Paragraph (a)(3)(v)(A) —Specific Components for Water Source Heat Pumps Component Description Air Economizers An automatic system that enables a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather. Condenser Pumps/Valves/Fittings Additional components in the water circuit for water control or filtering. Condenser Water Reheat A heat exchanger located downstream of the indoor coil that heats the supply air during cooling operation using water from the condenser coil in order to increase the ratio of moisture removal to cooling capacity provided by the equipment. Desiccant Dehumidification Components An assembly that reduces the moisture content of the supply air through moisture transfer with solid or liquid desiccants. Desuperheater A heat exchanger located downstream of the compressor on the high-pressure vapor line that moves heat to an external source, such as potable water. Fire/Smoke/Isolation Dampers A damper assembly including means to open and close the damper mounted at the supply or return duct opening of the equipment. Grill Options Special grills used to direct airflow in unique applications (such as up and away from a rear wall). Indirect/Direct Evaporative Cooling of Ventilation Air Water is used indirectly or directly to cool ventilation air. In a direct system the water is introduced directly into the ventilation air and in an indirect system the water is evaporated in secondary air stream and the heat is removed through a heat exchanger. Non-Standard High-Static Indoor Fan Motors The standard indoor fan motor is the motor specified in the manufacturer's installation instructions for testing and shall be distributed in commerce as part of a particular model. A non-standard high-static motor is an indoor fan motor that is not the standard indoor fan motor and that is distributed in commerce as part of an individual model within the same basic model. For a non-standard high-static indoor fan motor(s) to be considered a specific component for a basic model (and thus subject to the provisions of paragraph (a)(3)(v)(A)( 2 ) of this section), the following 2 provisions must be met: 1. Non-standard high-static indoor fan motor(s) must meet the minimum allowable efficiency determined per section D.4.1 of AHRI 600-2023 (incorporated by reference, see § 429.4) for non-standard high-static indoor fan motors, or per section D.4.2 of AHRI 600-2023 for non-standard high-static indoor integrated fan and motor combinations. 2. If the standard indoor fan motor can vary fan speed through control system adjustment of motor speed, all non-standard high-static indoor fan motors must also allow speed control (including with the use of a variable-frequency drive). Powered Exhaust/Powered Return Air Fans A powered exhaust fan is a fan that transfers directly to the outside a portion of the building air that is returning to the unit, rather than allowing it to recirculate to the indoor coil and back to the building. A powered return fan is a fan that draws building air into the equipment. Process Heat Recovery/Reclaim Coils/Thermal Storage A heat exchanger located inside the unit that conditions the equipment's supply air using energy transferred from an external source using a vapor, gas, or liquid. Refrigerant Reheat Coils A heat exchanger located downstream of the indoor coil that heats the supply air during cooling operation using high-pressure refrigerant in order to increase the ratio of moisture removal to cooling capacity provided by the equipment. Sound Traps/Sound Attenuators An assembly of structures through which the supply air passes before leaving the equipment or through which the return air from the building passes immediately after entering the equipment for which the sound insertion loss is at least 6 dB for the 125 Hz octave band frequency range. Steam/Hydronic Heat Coils Coils used to provide supplemental heating. Ventilation Energy Recovery System (VERS) An assembly that preconditions outdoor air entering the equipment through direct or indirect thermal and/or moisture exchange with the exhaust air, which is defined as the building air being exhausted to the outside from the equipment. Waterside Economizer A heat exchanger located upstream of the indoor coil that conditions the supply air when system water loop conditions are favorable so as not to utilize compressor operation. (B) The represented value of cooling capacity must be between 95 percent and 100 percent of the mean of the cooling capacities measured for the units in the sample selected as described in paragraph (a)(1)(ii) of this section, or between 95 percent and 100 percent of the cooling capacity output simulated by the AEDM as described in paragraph (a)(2) of this section. (vi) Commercial package air conditioning and heating equipment (excluding air-cooled equipment with a cooling capacity less than 65,000 Btu/h). Before May 15, 2025, the provisions in 10 CFR 429.43, revised as of January 1, 2024, are applicable. On and after May 15, 2025, when certifying to energy conservation standards in terms of EER or IEER and (as applicable) COP, the provisions in paragraph (a)(3)(vi)(B) of this section apply. When certifying to energy conservation standards in terms of IVEC and (as applicable) IVHE, all provisions in this paragraph (a)(3)(vi) apply. (A) For individual model selection when certifying to energy conservation standards in terms of IVEC and (as applicable) IVHE: ( 1 ) Representations for a basic model must be based on the least-efficient individual model(s) distributed in commerce among all otherwise comparable model groups comprising the basic model, with selection of the least-efficient individual model considering all options for factory-installed components and manufacturer-supplied components for field installation, except as provided in paragraph (a)(3)(vi)(A)( 2 ) of this section for individual models that include components listed in table 7 to paragraph (a)(3)(vi)(A) of this section. For the purpose of this paragraph (a)(3)(vi)(A)( 1 ), “otherwise comparable model group” means a group of individual models distributed in commerce within the basic model that do not differ in components that affect energy consumption as measured according to the applicable test procedure specified at 10 CFR 431.96 other than those listed in table 7 to paragraph (a)(3)(vi)(A) of this section. An otherwise comparable model group may include individual models distributed in commerce with any combination of the components listed in table 7 (or none of the components listed in table 7). An otherwise comparable model group may consist of only one individual model. ( 2 ) For a basic model that includes individual models distributed in commerce with components listed in table 7 to paragraph (a)(3)(vi)(A) of this section, the requirements for determining representations apply only to the individual model(s) of a specific otherwise comparable model group distributed in commerce with the least number (which could be zero) of components listed in table 7 to paragraph (a)(3)(vi)(A) included in individual models of the group. Testing under this paragraph (a)(3)(vi)(A)( 2 ) shall be consistent with any component-specific test provisions specified in section 6 of appendix A1 to subpart F of 10 CFR part 431. Table 7 to Paragraph ( a )(3)( vi )(A)—Specific Components for Commercial Package Air Conditioning and Heating Equipment [Excluding air-cooled equipment with a cooling capacity of less than 65,000 Btu/h] Component Description Air Economizers An automatic system that enables a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mild or cold weather. Desiccant Dehumidification Components An assembly that reduces the moisture content of the supply air through moisture transfer with solid or liquid desiccants. Evaporative Pre-cooling of Air-cooled Condenser Intake Air Water is evaporated into the air entering the air-cooled condenser to lower the dry-bulb temperature and thereby increase efficiency of the refrigeration cycle. Fire/Smoke/Isolation Dampers A damper assembly including means to open and close the damper mounted at the supply or return duct opening of the equipment. Indirect/Direct Evaporative Cooling of Ventilation Air Water is used indirectly or directly to cool ventilation air. In a direct system, the water is introduced directly into the ventilation air, and in an indirect system, the water is evaporated in secondary air stream, and the heat is removed through a heat exchanger. Non-Standard Ducted Condenser Fans (not applicable to Double-duct Systems) A higher-static condenser fan/motor assembly designed for external ducting of condenser air that provides greater pressure rise and has a higher rated motor horsepower than the condenser fan provided as a standard component with the equipment. Non-Standard High-Static Indoor Fan Motors The standard indoor fan motor is the motor specified in the manufacturer's installation instructions for testing and shall be distributed in commerce as part of a particular model. A non-standard motor is an indoor fan motor that is not the standard indoor fan motor and that is distributed in commerce as part of an individual model within the same basic model. For a non-standard high-static indoor fan motor(s) to be considered a specific component for a basic model (and thus subject to the provisions of paragraph (a)(3)(vi)(A)( 2 ) of this section), the following provisions must be met: (1) Non-standard high-static indoor fan motor(s) must meet the minimum allowable efficiency determined per section D.3.1 of AHRI 1340-2023 (incorporated by reference, see § 429.4) for non-standard high-static indoor fan motors or per section D.3.2 of AHRI 1340-2023 for non-standard high-static indoor integrated fan and motor combinations. (2) If the standard indoor fan motor can vary fan speed through control system adjustment of motor speed, all non-standard high-static indoor fan motors must also allow speed control (including with the use of variable-frequency drive). Powered Exhaust/Powered Return Air Fans A powered exhaust fan is a fan that transfers directly to the outside a portion of the building air that is returning to the unit, rather than allowing it to recirculate to the indoor coil and back to the building. A powered return fan is a fan that draws building air into the equipment. Process Heat recovery/Reclaim Coils/Thermal Storage A heat exchanger located inside the unit that conditions the equipment's supply air using energy transferred from an external source using a vapor, gas, or liquid. Refrigerant Reheat Coils A heat exchanger located downstream of the indoor coil that heats the supply air during cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to cooling capacity provided by the equipment. Sound Traps/Sound Attenuators An assembly of structures through which the supply air passes before leaving the equipment or through which the return air from the building passes immediately after entering the equipment for which the sound insertion loss is at least 6 dB for the 125 Hz octave band frequency range. Steam/Hydronic Heat Coils Coils used to provide supplemental heating. Ventilation Energy Recovery System (VERS) An assembly that preconditions outdoor air entering the equipment through direct or indirect thermal and/or moisture exchange with the exhaust air, which is defined as the building air being exhausted to the outside from the equipment. (B) The represented value of total cooling capacity must be between 95 percent and 100 percent of the mean of the total cooling capacities measured for the units in the sample selected as described in paragraph (a)(1)(ii) of this section, or between 95 percent and 100 percent of the total cooling capacity output simulated by the AEDM as described in paragraph (a)(2) of this section. (C) Representations of IVEC and IVHE (including IVHE c , as applicable) must be determined using a minimum part-load airflow that is no lower than the highest of the following: ( 1 ) The minimum part-load airflow obtained using the as-shipped system control settings; ( 2 ) The minimum part-load airflow obtained using the default system control settings specified in the manufacturer installation instructions (as applicable); and ( 3 ) The minimum airflow rate specified in section 5.18.2 of AHRI 1340-2023. (b) Certification reports. (1) The requirements of § 429.12 are applicable to commercial HVAC equipment; and (2) Pursuant to § 429.12(b)(13), a certification report must include the following public equipment-specific information: (i) Commercial package air-conditioning equipment (except commercial package air conditioning equipment that is air-cooled with a cooling capacity less than 65,000 Btu/h): (A) When certifying compliance with an EER standard: the energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), the rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model ( e.g., electric, gas, hydronic, none). (B) When certifying compliance with an IEER standard: the integrated energy efficiency ratio (IEER in British thermal units per Watt-hour (Btu/Wh)), the rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model ( e.g., electric, gas, hydronic, none). (ii) Commercial package heating equipment (except commercial package heating equipment that is air-cooled with a cooling capacity less than 65,000 Btu/h): (A) When certifying compliance with an EER standard: the energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), the coefficient of performance (COP), the rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model ( e.g., electric, gas, hydronic, none). (B) When certifying compliance an IEER standard: the integrated energy efficiency ratio (IEER in British thermal units per Watt-hour (Btu/Wh)), the coefficient of performance (COP), the rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model ( e.g., electric, gas, hydronic, none). (iii) Packaged terminal air conditioners: The energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), the rated cooling capacity in British thermal units per hour (Btu/h), the wall sleeve dimensions in inches (in), and the duration of the break-in period (hours). (iv) Packaged terminal heat pumps: The energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/W-h)), the coefficient of performance (COP), the rated cooling capacity in British thermal units per hour (Btu/h), the wall sleeve dimensions in inches (in), and the duration of the break-in period (hours). (v) Single package vertical air conditioners: (A) When certifying compliance with an EER standard: The energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), and the rated cooling capacity in British thermal units per hour (Btu/h). (B) When certifying compliance with an IEER standard: the integrated energy efficiency ratio (IEER in British thermal units per Watt-hour (Btu/Wh)), the rated cooling capacity in British thermal units per hour (Btu/h), and the rated airflow in standard cubic feet per minute (SCFM). For units with rated cooling capacity <65,000 Btu/h: whether the unit is weatherized or non-weatherized; and if non-weatherized, the airflow rate of outdoor ventilation air which is drawn in and conditioned as determined in accordance with § 429.134(x)(3), while the equipment is operating with the same drive kit and motor settings used to determine the certified efficiency rating of the equipment. (vi) Single package vertical heat pumps: (A) When certifying compliance with an EER standard: the energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), and the coefficient of performance (COP), and the rated cooling capacity in British thermal units per hour (Btu/h). (B) When certifying compliance with an IEER standard: the integrated energy efficiency ratio (IEER in British thermal units per Watt-hour (Btu/Wh)), and the coefficient of performance (COP), the rated cooling capacity in British thermal units per hour (Btu/h), and the rated airflow in standard cubic feet per minute (SCFM). For units with cooling capacity <65,000 Btu/h: whether the unit is weatherized or non-weatherized; and if non-weatherized, the airflow rate of outdoor ventilation air which is drawn in and conditioned as determined in accordance with § 429.134(x)(3), while the equipment is operating with the same drive kit and motor settings used to determine the certified efficiency rating of the equipment. (vii) Variable refrigerant flow multi-split air-cooled air conditioners (other than air-cooled with rated cooling capacity less than 65,000 btu/h): (A) When certifying compliance with an EER standard: The energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model (e.g., electric, gas, hydronic, none). (B) When certifying compliance with an IEER standard, the following must be certified for each tested combination as required under paragraph (a)(3)(ii)(C) of this section: The integrated energy efficiency ratio (IEER) in British thermal units per Watt-hour (Btu/Wh)); the rated cooling capacity in British thermal units per hour (Btu/h); whether the represented values are for a non-ducted, ducted, or SDHV tested combination, or for a mixed representation of any two of the tested combinations; and the outdoor unit(s) and indoor units identified in the tested combination. The following must be certified for each basic model: the type(s) of heating used ( i.e., electric, gas, hydronic, none); and the refrigerant used to determine the represented values. (viii) Variable refrigerant flow multi-split heat pumps (other than air-cooled with rated cooling capacity less than 65,000 btu/h): (A) When certifying compliance with an EER standard: The energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), the coefficient of performance (COP), rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model (e.g., electric, gas, hydronic, none). (B) When certifying compliance with an IEER standard, the following must be certified for each tested combination as required under paragraph (a)(3)(ii)(C) of this section: The integrated energy efficiency ratio (IEER) in British thermal units per Watt-hour (Btu/Wh); the coefficient of performance (COP); the rated cooling capacity in British thermal units per hour (Btu/h); the rated heating capacity (Btu/h); whether the represented values are for a non-ducted, ducted, or SDHV tested combination, or for a mixed representation of any two of the tested combinations; and the outdoor unit(s) and indoor units identified in the tested combination. The following must be certified for each basic model: the type(s) of heating used ( i.e., electric, gas, hydronic, none); and the refrigerant used to determine the represented values. (ix) Computer room air-conditioners: (A) When certifying compliance with a SCOP standard: The net sensible cooling capacity in British thermal units per hour (Btu/h), the net cooling capacity in British thermal units per hour (Btu/h), the configuration (upflow/downflow), economizer presence (yes or no), condenser medium (air, water, or glycol-cooled), sensible coefficient of performance (SCOP), and rated airflow in standard cubic feet per minute (SCFM). (B) When certifying compliance with an NSenCOP standard: The net sensible cooling capacity in British thermal units per hour (Btu/h), the net total cooling capacity in British thermal units per hour (Btu/h), whether the basic model is split system or single-package, the configuration (downflow, upflow ducted, upflow non-ducted, horizontal flow, ceiling-mounted ducted, ceiling-mounted non-ducted), fluid economizer presence (yes or no), condenser heat rejection medium (air, water, or glycol-cooled), net sensible coefficient of performance (NSenCOP), rated airflow in standard cubic feet per minute (SCFM), and the refrigerant used to determine the represented values. (x) Water source heat pumps (other than variable refrigerant flow): The energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/Wh)), the coefficient of performance (COP), the rated cooling capacity in British thermal units per hour (Btu/h), and the type(s) of heating used by the basic model (e.g., electric, gas, hydronic, none). (xi) Direct-expansion dedicated outdoor air systems: (A) When certifying compliance with an ISMRE2 standard: the integrated seasonal moisture removal efficiency 2 (ISMRE2 in lbs. of moisture per kilowatt-hour (lb/kWh)), the rated moisture removal capacity at Standard Rating Condition A according to appendix B to subpart F of part 431 of this chapter (MRC in lbs of moisture per hour (lb/h)), and the rated supply airflow rate for 100 percent outdoor air applications (Q SA in standard cubic feet per minute). (B) When certifying compliance with an ISCOP2 standard: the integrated seasonal coefficient of performance 2 (ISCOP2 in Watts of heating per Watts of power input (W/W)). (C) The configuration of the basic model number ( i.e., “single-package” or “split system”) shall also be provided. (3) Pursuant to § 429.12(b)(13), a certification report must include the following additional equipment-specific information: (i) Whether the basic model is engineered-to-order; and (ii) For any basic model rated with an AEDM, whether the manufacturer elects the witness test option for verification testing. (See § 429.70(c)(5)(iii) for options). However, the manufacturer may not select more than 10% of AEDM-rated basic models. (iii) For direct-expansion dedicated outdoor air systems with ventilation energy recovery systems, method of determination of the exhaust air transfer ratio (EATR), sensible effectiveness, and latent effectiveness of the ventilation energy recovery system (name and version of certified performance modeling software or if the device was directly tested). The test method ( i.e., Option 1 or Option 2) for units rated based on testing and motor control settings (including rotational speed) for energy recovery wheels shall also be provided. (4) Pursuant to § 429.12(b)(13), a certification report must include supplemental information submitted in PDF format. The equipment-specific, supplemental information must include any additional testing and testing set up instructions ( e.g., charging instructions) for the basic model; identification of all special features that were included in rating the basic model; and all other information ( e.g., operational codes or component settings) necessary to operate the basic model under the required conditions specified by the relevant test procedure. A manufacturer may also include with a certification report other supplementary items in PDF format ( e.g., manuals) for DOE consideration in performing testing under subpart C of this part. The equipment-specific, supplemental information must include at least the following: (i) Commercial package air-conditioning equipment (except commercial package air conditioning equipment that is air-cooled with a cooling capacity less than 65,000 Btu/h): rated indoor airflow in standard cubic feet per minute (SCFM) for each fan coil; water flow rate in gallons per minute (gpm) for water-cooled units only; rated external static pressure in inches of water; frequency or control set points for variable speed components ( e.g., compressors, VFDs); required dip switch/control settings for step or variable components; a statement whether the model will operate at test conditions without manufacturer programming; any additional testing instructions, if applicable; and if a variety of motors/drive kits are offered for sale as options in the basic model to account for varying installation requirements, the model number and specifications of the motor (to include efficiency, horsepower, open/closed, and number of poles) and the drive kit, including settings, associated with that specific motor that were used to determine the certified rating. When certifying compliance with an IEER standard, rated indoor airflow in SCFM for each part-load point used in the IEER calculation and any special instructions required to obtain operation at each part-load point, such as frequency or control set points for variable speed components ( e.g., compressors, VFDs), dip switch/control settings for step or variable components, or any additional applicable testing instructions, are also required. (ii) Commercial package heating equipment (except commercial package heating equipment that is air-cooled with a cooling capacity less than 65,000 Btu/h): The rated heat…

    Related guides, FAQ and contract templates