Beta
HK Cap. 311I
HK Cap. 311I — Air Pollution Control (Fuel Restriction) Regulations
Beta. Legal information, not legal advice. LEGALDIGM is not a law firm. Check the official source for the current text.
Analyze this law with AIAir
Pollution
Control
(Fuel
Restriction)
Regulations ( Cap.
311,
section
43 ) (Enacting provision omitted— E.R. 5 of
2022 ) [1 July 1990] (Format changes— E.R. 5 of 2022 ) 1. Citation ( E.R. 5 of 2022 )
(1) These regulations may be cited as the Air Pollution Control (Fuel Restriction)
Regulations.
(2) (Omitted as spent— E.R. 5 of 2022 ) 2. Interpretation
In these regulations, unless the context otherwise requires—
competent
examiner
( 合資格檢驗師 ) means a registered professional engineer
in the building services, gas, chemical, environmental, marine and naval architecture or
mechanical discipline under the Engineers Registration Ordinance ( Cap. 409 );
( L.N. 123 of 2008 )
conventional
solid
fuel
( 常規固體燃料 ) has the same meaning as in
regulation 3(2) of the Air Pollution Control (Furnaces, Ovens and
Chimneys) (Installation and Alteration) Regulations ( Cap. 311
sub. leg. A );
( L.N. 123 of 2008 )
electricity
works
( 電力工程 ) means the process specified in item 7 of
the First Schedule to the Ordinance as “Electricity Works” and described
therein;
restricted
liquid
fuel
( 受限制液體燃料 ) means any liquid fuel that
has—
(a) a sulphur content of more than
0.001%
by weight; or
( L.N. 165 of 2024 )
(b) a viscosity of more than 6 centistokes at 40 o C;
( L.N. 123 of 2008 )
specified
emission
limit
( 指明排放限度 ), in relation to a specified pollutant,
means the emission limit specified in column 2 of Schedule 1 opposite the
pollutant; ( L.N. 123 of 2008 )
specified
pollutant
( 指明污染物 ) means sulphur dioxide, nitrogen oxides or
respirable suspended particulates;
( L.N. 123 of 2008 )
viscosity
( 黏度 ) has the same meaning as in regulation
2 of the Air Pollution Control (Dust and Grit Emission) Regulations ( Cap. 311 sub. leg. B ). ( L.N. 165 of 2024 ) 3. Application
These regulations do not apply to—
(a)
any relevant plant that— (i) is used or operated in premises used solely as a dwelling; (ii) is used or operated in or on a vessel, motor vehicle, railway locomotive or
aircraft; or (iii) is used or operated in premises used solely for the conduct of electricity
works and in respect of which premises the owner thereof is the holder of a
licence granted under section 15(1) of the Ordinance prior to the
commencement
date *
of these regulations or is exempt under section
20(1) of the Ordinance in respect of those works from the operation of
section 13 of the Ordinance prior to that date; or
(b) the use or consumption of gaseous fuel.
Editorial Note:
* Commencement date: 1 July
1990.
4. (Repealed L.N. 165 of 2024 ) 4A. Restriction on use of restricted liquid fuel in relevant
plants ( L.N. 165 of 2024 ) Subject to regulation 4B ,
a
person must not use restricted liquid fuel in a relevant
plant. ( L.N. 123 of
2008 ; L.N. 165 of 2024 ) 4B. Restricted liquid fuel may be used in relevant plants issued with certificates of compliance
(1)
A person may use restricted liquid fuel in a relevant plant if—
( L.N. 165 of 2024 )
(a) a competent examiner has issued a certificate of compliance in respect of
the plant within the preceding 12 months, and the certificate is
valid;
(b) the certificate is displayed at a conspicuous position of the
plant;
(c) the plant is located at the premises set out in the certificate pursuant to
subregulation (3)(a) ;
(d) the plant is of the type, and bears the identification number, set out in
the certificate pursuant to subregulation (3)(b) ; and
(e)
as stated in the certificate pursuant to subregulation
(3)(c) — (i) the plant is not installed or used with an emission control device;
or (ii) the plant is installed or used with an emission control device that is
of the type, bears the identification number, and complies with the working
principle, set out in the certificate.
(2)
A competent examiner shall not issue a certificate of compliance in respect of a relevant plant unless—
(a) the examiner has carried out a test on the level of each specified pollutant emitted from the plant when the plant was operating at maximum operating capacity using restricted liquid fuel;
(b) the level of each specified pollutant emitted from the plant during the test did not exceed the specified emission limit for it; and
(c)
the test was carried out— (i) in accordance with the test methods and measurement requirements set out in Schedule 2 ; and (ii) within 14 days before the date on which the certificate is issued.
(3)
Subject to subregulation (4), a certificate of compliance issued in respect of a relevant plant is required to include the following information—
(a) the address of the premises where the plant is located;
(b) the type and identification number of the plant;
(c) whether an emission control device is installed in or used with the plant and, if so, the type, identification number, working principle and operation and maintenance requirements of the device;
(d) the means of determining the fuel consumption rate of the plant during the test;
(e) the removal efficiency for each specified pollutant at maximum fuel consumption rate of the plant during the test;
(f) the maximum sulphur content and viscosity of the restricted liquid fuel that may be used if the level of each specified pollutant emitted from the plant at maximum fuel consumption rate of the plant is not to exceed the specified emission limit for it;
(g) the date of issue and the validity period of the certificate; and
(h) the name and contact details of the competent examiner.
(4) For the purposes of ascertaining whether an emission control device installed in or used with a relevant plant will function properly during the validity period of a certificate of compliance issued in respect of the plant, a competent examiner may require that the removal efficiency for each specified pollutant at maximum fuel consumption rate of the plant is to be measured during that period at the frequency, and in accordance with the means, specified by the examiner. In that case, the certificate is also required to state the requirement, and the frequency and means so specified.
(5) A competent examiner shall not issue a certificate of compliance that contains any statement or information which he knows or reasonably ought to know to be false or misleading in a material particular. ( L.N. 123 of 2008 ) 4C. Duties of persons using restricted liquid fuel in relevant plants and owners of relevant plants
(1)
A person who uses restricted liquid fuel in a relevant plant under regulation 4B(1) shall ensure that—
(a) the plant is properly operated and maintained;
(b)
the emission control device installed in or used with the plant, if any— (i) complies with the operation and maintenance requirements of the device set out in the certificate of compliance pursuant to regulation 4B(3)(c) ; and (ii) is properly operated and maintained;
(c)
if the certificate states that the removal efficiency for each specified pollutant at maximum fuel consumption rate of the plant is required to be measured during its validity period— (i) the removal efficiency is measured at the frequency, and in accordance with the means, set out in the certificate pursuant to regulation 4B(4) ; and (ii) the removal efficiency from the measurement is not lower than that set out in the certificate pursuant to regulation 4B(3)(e) ; and
(d) the sulphur content and viscosity of the restricted liquid fuel used do not exceed their respective maximum limit set out in the certificate pursuant to regulation 4B(3)(f) .
(2)
The owner of a relevant plant shall—
(a) keep, or cause to be kept, a certificate of compliance issued in respect of the plant for a period of 3 years after issue; and
(b) produce, or cause to be produced, the certificate for inspection on request by the Authority during the period of 3 years. ( L.N. 123 of 2008 ) 4D. Restriction on use of conventional solid fuel in relevant
plants ( L.N. 165 of 2024 ) A
person must not use conventional solid fuel that has a sulphur content
of more than 1% by weight in a relevant
plant. ( L.N. 123 of
2008 ; L.N. 165 of 2024 ) 5. Offence
(1) Any person who contravenes
regulation
4A , 4C(1) or 4D commits an offence
and is liable to a fine
at
level 4 and imprisonment for 6 months, and in addition, to a fine
not exceeding $5,000 for each day during the whole or any part of which the offence
continues. ( L.N. 123 of
2008 ; E.R. 5 of
2022 ; L.N. 165 of 2024 )
(2)
A competent examiner who contravenes regulation 4B(2) or (5) commits an offence and is liable—
(a) on a first conviction, to a fine at level 5; and
(b) on a subsequent conviction, to a fine at level 5 and to imprisonment for 3 months. ( L.N. 123 of 2008 )
(3)
The owner of a relevant plant who contravenes regulation 4C(2) commits an offence and is liable—
(a) on a first conviction, to a fine at level 5; and
(b) on a subsequent conviction, to a fine at level 5 and to imprisonment for 3 months. ( L.N. 123 of 2008 ) 6. (Omitted as spent— E.R. 5 of 2022 ) 7. (Omitted as spent— E.R. 5 of 2022 ) Schedule
1 [ reg.
2 ] Specified
Emission
Limit
Specified
pollutant
Emission
limit
(gram
pollutant per litre fuel)
Sulphur dioxide
0.864
Nitrogen oxides*
2.4
Respirable suspended particulates
0.12
* expressed as nitrogen
dioxide ( Schedule 1 added L.N. 123 of 2008 ) Schedule
2 [ reg. 4B ] Test Methods
and
Measurement
Requirements 1.
The actual volumetric flow rate of flue gas in cubic metres per hour
(m 3 /hr) and the actual concentration of specified pollutants in grams
per cubic metre (g/m 3 ) are required to be tested and measured at the same
time using the following methods (which are listed in Appendix M to Part
51 and Appendix A to Part 60 of Title 40 of the Code of Federal
Regulations published in the Federal Register of the United States
Government)—
(a) determination of the actual volumetric flow rate of flue gas— Method 2—Determination of
stack gas velocity and volumetric flow rate (Type S pitot tube);
(b) determination of the actual concentration of sulphur dioxide— Method 6—Determination of
sulfur dioxide emissions from stationary sources; or Method 6C—Determination of
sulfur dioxide emissions from stationary sources (instrumental analyzer
procedure);
(c) determination of the actual concentration of nitrogen oxides— Method 7—Determination of
nitrogen oxide emissions from stationary sources; or Method 7E—Determination of
nitrogen oxides emissions from stationary sources (instrumental analyzer
procedure);
(d)
determination of the actual concentration of respirable suspended
particulates— (i) if water droplets do not exist in emissions from the relevant
plant— Method 201—Determination
of PM 10 Emissions (Exhaust Gas Recycle
Procedure); or Method 201A—Determination
of PM 10 Emissions (Constant Sampling
Rate Procedure); (ii) if water droplets exist in emissions from the relevant plant— Method 5—Determination of
particulate matter emissions from stationary
sources. 2. The flow rate of fuel consumption in litres per hour (L/hr) is required to be
measured at the same time when the actual volumetric flow rate of flue gas and the
actual concentration of each specified pollutant are
measured. 3. The level of each specified pollutant emitted from the relevant plant is
required to be determined using the following formula— actual volumetric flow rate of flue gas (m 3 /hr) × actual
concentration of specified pollutant (g/m 3 ) ÷ flow rate of fuel
consumption (L/hr). ( Schedule 2 added L.N. 123 of